Home ProductsGas Insulated Switchgear

HXGN15 GIS SF6 MV Ring Main Unit RMU Electrical Panel

Certification
China Knkong Electric Co.,Ltd certification
China Knkong Electric Co.,Ltd certification
I'm Online Chat Now

HXGN15 GIS SF6 MV Ring Main Unit RMU Electrical Panel

HXGN15 GIS SF6 MV Ring Main Unit RMU Electrical Panel
HXGN15 GIS SF6 MV Ring Main Unit RMU Electrical Panel

Large Image :  HXGN15 GIS SF6 MV Ring Main Unit RMU Electrical Panel

Product Details:
Place of Origin: China
Brand Name: Knkong
Certification: IEC ISO
Model Number: GIS
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: USD 2000-10000
Packaging Details: Standard export packaging
Delivery Time: 30 days
Payment Terms: L/C, T/T
Supply Ability: 100 Unit per month

HXGN15 GIS SF6 MV Ring Main Unit RMU Electrical Panel

Description
Rated Voltage: 12/24/36KV Rated Current: 630A 1250A
Rated Frequency: 50Hz Standards: GB ISO
OEM/ODM: Inquiry By Email Manufactory: KNKONG
High Light:

GIS SF6 MV Ring Main Unit

,

HXGN15 MV Ring Main Unit

,

SF6 RMU Electrical Panel

GIS SF6 model HXGN15 series Switchgear 12/24/36KV 630A 1250A M.V panel GB ISO

 

Product Introduction

 

General

The so-called "ring network cabinet" means that each distribution branch is equipped with a switch cabinet (outgoing switch cabinet), and the busbar of this switch cabinet is also a part of the ring trunk. In other words, the ring trunk line is composed of the bus bars of each outlet cabinet. Each outlet cabinet is called a "ring network cabinet". In fact, if you take out a ring network cabinet alone, you can't see the meaning of "ring network".

 

Protection device
On the basis of many years of application experience of domestic and foreign counterparts in the microcomputer protection device of the ring network cabinet, combined with the actual characteristics of the domestic integrated automation system, the development of a high-tech power automation product integrating protection, monitoring, control, communication and other functions is a composition Ideal electrical unit for intelligent switchgear. The product has a built-in protection library composed of more than 20 standard protection programs, which has a complete and powerful collection function of the voltage, current analog quantity and switch quantity of the primary equipment (current measurement is realized through the protection CT).
Microcomputer protection
Since the ring main unit is subjected to high voltage, a protection device is required to protect the ring main unit. The use of microcomputer protection devices in the ring main unit is becoming more and more popular. Due to the small size and low cost of the ring main unit, it is necessary to have a cost-effective and practical microcomputer protection device.

 

Service Environment
1. Air temperature: -35℃~+40℃
2. Humidity: Monthly average humidity 95%; Daily average humidity 90%.
3. Altitude:≤ 2500m
4. Ambient air not apparently polluted by corrosive and flammable gas, vapor, etc.
5. No frequent violent shake

 

Technical Data

No. Item Unit Parameter
1 Rated voltage kV 12 24 36
2 Rated frequency Hz 50/60
3 Rated current A 630(1250*)
4

1min Power frequency

withstand voltage

wet kV 38 50 70
dry kV 48 60 85
5 Lightning impulse withstand voltage kV 75 125/150 170
6 Rated short circuit breaking current (peak) kA 80 63 63
7 Rated active load and close circuit breaking current A 63 50 50
8 Rated transferring current A 1700 1200 1200
9 Rated short circuit making a current (peak) kA 80 63 63
10 Rated cable(line) charging breaking current A

50 and 10

50/10

11 Cable charge breaking current in earthing fault A 20 20 20
12 Rated withstand current (peak) kA 80 63 63
13 Short-time withstand current (2s) kA 25 20 20
14 Mechanism life times 5000 2000 2000

Note: For short circuit breaking and the peak current is based on Fuse plus combination

HXGN15 GIS SF6 MV Ring Main Unit RMU Electrical Panel 0HXGN15 GIS SF6 MV Ring Main Unit RMU Electrical Panel 1HXGN15 GIS SF6 MV Ring Main Unit RMU Electrical Panel 2HXGN15 GIS SF6 MV Ring Main Unit RMU Electrical Panel 3